Project status: Research & Development
Purpose
Test signal/Phantom power source Energoforma-61850 is meant for testing and calibration of the following instruments:
- meters according to IEC 62053-21:2003;
- PQ analyzers according to IEC 62586-1 and IEC 62586-2 (Flicker, harmonics, interharmonics, subharmonics, dips, swells);
- standalone Merging Units (SAMU) according to IEC 61869-13;
- PMU according to IEEE С37.118.1 and С37.118.1А (Types of modulation: amplitude, phase, frequency, additive).
Energoforma-61850 can be applied as part of reference setups such as our mobile multifunctional reference setup MarsTest-61850.
DESCRIPTION:
Energoforma-61850 monoblock design assures high sealing capability and fully meets IP67 requirements. The front panel contains the following:
- Ethernet port SFP for 61850-9-2LE input data;
- 2 Ethernet ports (RJ-45) for PC connection and synchronization;
- 8 voltage outputs used to imitate signals from electronic transformers (4 ~ Uout, 4 ~ Iout) 0.2 mV ÷ 8 V;
- 4 current outputs 1 mA ÷ 10 A;
- 4 current outputs 10 A ÷ 120 A;
- 4 voltage outputs 1 V ÷ 264 V;
- Frequency inputs/outputs for synchronization with an external source or receiver;
PC-based software is used to control Energoforma-61850.
Operation modes
Digital streams SV61850-9-2 are converted into analogue current or voltage waveforms.
Analogue signals are digitally synthesized from user-specified parameters (a modulating signal can be added).